PAW.HD950 hydraulic separator for horizontal distribution manifold DN 20, up to 950 l/h – SALE
Code: 3142Product detailed description
The PAW.HD950 (code 3142) is a hydraulic separator from the PAW system for installations with a DN 20 horizontal distribution manifold. It balances pressures and flow rates between the primary heat source circuit and the secondary consumer circuits, so the pumps of the individual circuits do not affect each other. The boiler circuit then runs at a constant flow rate and the heating circuits at a variable one.
Connection and installation
- heat source side: 3/4" female or 1" male thread with flat seal
- system side: 3/4" PAW flange for a 1" union nut – directly onto the PAW.MV 20 manifold
- 2 x 3/4" female ends with plugs, for example for a temperature sensor or a drain ball valve
- mounting horizontally below the triple PAW.MV manifold, vertically, or on its own in the pipework (2 nuts code 2055 are then required)
Design
- brass body, EPDM seals, design EPP insulation
- width 430 mm, height 80 mm, connection centre distance 90 mm
- supplied with separator body, insulation, union nuts and sealing plugs
When a separator is used, the primary circuit and every secondary circuit must have their own circulation pump. EPDM seals must not come into contact with substances containing mineral oils. Optional accessories include PAW.DR 3121 wall brackets and the PAW.KEX 7509 expansion vessel connection kit.
Technical data
| Code | 3142 |
| Manufacturer | PAW |
| Type | PAW.HD950 |
| Nominal size | DN 20 |
| Recommended flow rate | up to 950 l/h |
| Max. operating pressure | 6 bar |
| Max. operating temperature | +110 °C |
| Heat source connection | 3/4" female or 1" male |
| Manifold connection | PAW flange 3/4", 1" union nut |
| Side connections | 2 x 3/4" female with plug |
| Dimensions (W x H) | 430 x 80 mm |
| Connection centre distance | 90 mm |
| Material | brass, EPP insulation, EPDM seals |
Frequently asked questions
When is a hydraulic separator needed?
When the system has a pump on the heat source side and pumps in the consumer circuits that must not influence each other. Every circuit, primary and secondary, needs its own circulation pump.
Can the PAW.HD950 be installed without a manifold?
Yes, the separator can be fitted on its own in the pipework; two union nuts code 2055 are then needed. It works in both horizontal and vertical position.
How is the separator connected when mounted vertically?
The heating circuits connect to the upper connection and the boiler circuit to the lower one. The drain ball valve is then fitted in the bottom end, the lowest point.
Additional parameters
| Category: | hydraulic separators |
|---|---|
| Warranty: | 2 years |
| Code: | 3142 |
| Manufacturer: | PAW |
| Type: | PAW.HD950 |
| Nominal size: | DN 20 |
| Recommended flow rate: | up to 950 l/h |
| Max. operating pressure: | 6 bar |
| Max. operating temperature: | +110 °C |
| Heat source connection: | 3/4" female or 1" male |
| Manifold connection: | PAW flange 3/4", 1" union nut |
| Side connections: | 2 x 3/4" female with plug |
| Dimensions (W x H): | 430 x 80 mm |
| Connection centre distance: | 90 mm |
| Material: | brass, EPP insulation, EPDM seals |