Stainless steel hydraulic separator ERMETIQ 4 × 1" with insulation, up to 45 kW
Code: ERM_ER-HS7622Product detailed description
The hydraulic separator ERMETIQ ER-HS7622 separates the primary heating circuit from the secondary one and at the same time balances the pressure and flow between them. This allows the circulation pumps to operate independently without interfering with each other, resulting in a more stable and efficient operation of the entire system. This model with the designation 4 × 1" is suitable for heating systems with a thermal output of up to 45 kW.
Main Features
- hydraulic separation of the primary and secondary circuits
- balancing of pressure and flow conditions between the circuits
- independent operation of circulation pumps without mutual interference
- integrated strainer captures mechanical impurities and allows them to settle in the lower part of the body
- drain valve for easy removal of deposits from the system
- reversible design allows connection from the left or right side
- body made of stainless steel SUS304 with high corrosion resistance
- thermal insulation reduces heat loss and the packaging also includes a bracket for wall mounting
Technical Data
| Model | ER-HS7622 |
| Type | hydraulic separator |
| Maximum heating system output | 45 kW |
| Connection | 4 × 1" |
| Body material | stainless steel SUS304 |
| Thermal insulation | yes |
| Working medium | water or a mixture of water and ethylene glycol |
| Maximum working pressure | 10 bar |
| Operating temperature | 0 to +100 °C |
| Mounting | vertical, connection from the left or right side |
| Package contents | thermal insulation, mounting bracket, drain valve |
Application and Installation
The separator is installed between the heat source and the heating distribution, typically in a boiler room or technical room. It is mounted vertically and thanks to the reversible design, the supply can be connected from the left or right side, allowing you to adapt it to the layout of the distribution. You can secure it to the wall using the bracket included in the package and after installation, apply the thermal insulation. The strainer and drain valve ensure that impurities collected in the lower part of the body can be regularly drained from the system. It can be operated with water or a mixture of water and ethylene glycol, at a pressure of up to 10 bar and a temperature range from 0 to +100 °C.
Frequently Asked Questions
What is the purpose of a hydraulic separator in a heating system?
It separates the primary and secondary circuits, balances the flows and pressures between them, and allows the circulation pumps to operate without mutual interference.
Can the separator be used with a mixture of water and glycol?
Yes, the manufacturer specifies water or a mixture of water and ethylene glycol as the working medium at a temperature range from 0 to +100 °C.
Can I connect the supply from the right and left side?
Yes, the design is reversible, so connection from the left or right side is possible. The separator is mounted vertically.
Product rating
Be the first who will post an article to this item!
Discussion
Be the first who will post an article to this item!