Dry-rotor in-line pump DAB.CP2 40-2800 T, flanged, DN 40
Code: 60213582Product detailed description
DAB.CP2 40-2800 T (code 60213582) is a single dry-rotor in-line pump with a flanged DN 40 connection. According to its type key it reaches a maximum head of about 28 m (the number 2800 gives the head in cm). It is driven by a 2-pole three-phase asynchronous motor.
Applications
- Water circulation in heating and air-conditioning systems of commercial buildings, including systems with solar collectors
- Pumping clean, non-aggressive, non-viscous liquids free of solid and abrasive particles, with properties close to water
- Fixed installation directly in the pipeline, with suction and discharge on the same axis (in-line)
Construction
The pump casing and the adapter joining the motor to the pump are made of cast iron; the impeller is cast iron or technopolymer depending on the type. The shaft is sealed by a standard silicon carbide mechanical seal with EPDM O-rings, and the motor shaft is stainless steel. The motor is an air-cooled 2-pole three-phase asynchronous motor; the flanges are PN 10 or PN 16 with threaded ports for pressure gauges.
Series data
Series data from the manufacturer: operating range up to 105 m³/h with a head of up to 110 m, liquid temperature from −15 to +140 °C, ambient temperature up to +50 °C, maximum operating pressure 16 bar, glycol content up to 50 %, protection class IP 55, insulation class F, supply 3 × 230 V / 3 × 400 V, 50 Hz.
Installation and operation
Install the pump permanently in the pipeline, horizontally or vertically and always with the motor on top; pumps with motors from 7.5 kW upwards only vertically. Overload protection of the motor must be provided by the user, and the electrical connection should be made by a qualified person.
Technical data
| Code | 60213582 |
| Manufacturer | DAB |
| Type | DAB.CP2 |
| Model designation | 40-2800 T |
| Nominal flange size | DN 40 |
| Maximum head according to designation | ≈ 28 m |
| Motor | three-phase asynchronous, 2-pole |
| Supply | 3 × 230 V / 3 × 400 V, 50 Hz |
| Flanges | PN 10 / PN 16 |
| Liquid temperature | −15 … +140 °C |
| Maximum pressure | 16 bar |
| Protection class | IP 55 |
| Insulation class | F |
| Design | single pump, flanged |
Frequently asked questions
What liquid can the pump handle?
Clean, non-aggressive, non-viscous liquids free of solid and abrasive particles, with properties similar to water. The glycol content may be up to 50 %.
In what position is the pump installed?
Permanently in the pipeline, horizontally or vertically, with the motor above the pump. Pumps with motors from 7.5 kW upwards are installed vertically only.
What does the designation DAB.CP2 40-2800 T mean?
The DAB.CP2 series consists of single dry-rotor pumps with a 2-pole motor; 40 is the nominal flange size (DN), 2800 is the maximum head in cm (about 28 m) and T stands for a three-phase motor.
Additional parameters
| Category: | DAB.CP,CP-G,DCP,DCP-G - Dry-Rotor Pumps, 2-Pole |
|---|---|
| Warranty: | 2 years |
| Code: | 60213582 |
| Manufacturer: | DAB |
| Type: | DAB.CP2 |
| Model designation: | 40-2800 T |
| Nominal flange size: | DN 40 |
| Maximum head according to designation: | ≈ 28 m |
| Motor: | three-phase asynchronous, 2-pole |
| Supply: | 3 × 230 V / 3 × 400 V, 50 Hz |
| Flanges: | PN 10 / PN 16 |
| Liquid temperature: | −15 … +140 °C |
| Maximum pressure: | 16 bar |
| Protection class: | IP 55 |
| Insulation class: | F |
| Design: | single pump, flanged |
Product rating
Be the first who will post an article to this item!
Discussion
Be the first who will post an article to this item!