Twin-head dry-rotor pump DAB DCM2 50-1000 T 230/400/50, DN 50 flanges
Code: 60215274Product detailed description
DAB DCM2 50-1000 T 230/400/50 (code 60215274) is a twin-head dry-rotor pump from DAB in a flanged in-line design with DN 50 flanges. It is fitted straight into the pipe run and circulates water in the heating, air-conditioning and solar circuits of commercial buildings.
Hydraulics
- DN 50 flanges on suction and discharge side, PN 10 or PN 16, with threaded ports for check gauges
- the number 1000 in the type code is the maximum head in centimetres, i.e. about 10 m
- for the whole series the manufacturer states a flow of up to 105 m³/h and a head of up to 110 m
Motor
Air-cooled four-pole three-phase asynchronous motor, supply 3 × 230/400 V, 50 Hz, protection rating IP 55, insulation class F. Overload protection for the motor has to be provided by the user.
Materials
Pump casing and lantern are cast iron, the impeller is cast iron or technopolymer depending on the type. The shaft is stainless steel and the mechanical seal is silicon carbide (SiC/SiC) with EPDM seals to DIN 24960.
Operation and installation
The pumped liquid must be clean, free of solid and abrasive particles, non-viscous and non-aggressive. Permitted liquid temperature is −15 to +140 °C, glycol content up to 50 %, operating pressure up to 16 bar and ambient temperature up to +50 °C. The pump is installed in a fixed position, horizontally or vertically with the motor on top; motors of 7.5 kW and above vertically only. The electrical connection is a job for a qualified electrician.
Technical data
| Code | 60215274 |
| Manufacturer | DAB |
| Type | DAB.DCM2 |
| Model | DCM2 50-1000 T 230/400/50 |
| Design | twin-head, flanged, in-line |
| Flange nominal size | DN 50 (PN 10 / PN 16) |
| Max. head (per designation) | ≈ 10 m |
| Motor poles | 4 |
| Power supply | 3 × 230/400 V, 50 Hz |
| Liquid temperature | −15 … +140 °C |
| Max. glycol content | 50 % |
| Max. operating pressure | 16 bar |
| Protection rating / insulation class | IP 55 / F |
Frequently asked questions
What does the number 1000 in the designation DCM2 50-1000 T 230/400/50 mean?
It is the maximum head in centimetres, so according to the designation the pump reaches about 10 m. The actual duty point depends on the flow in the system.
Which liquids may the pump handle?
Clean water free of solid and abrasive particles, non-viscous and non-aggressive, at −15 to +140 °C and with up to 50 % glycol.
How is the pump installed?
Fixed in the pipe run, horizontally or vertically with the motor above the pump; motors of 7.5 kW and above vertically only. Electrical connection and motor protection are a job for a specialist.
Additional parameters
| Category: | DAB.CM,CM-G,DCM,DCM-G - Dry-Rotor Pumps, 4-Pole |
|---|---|
| Warranty: | 2 years |
| Code: | 60215274 |
| Manufacturer: | DAB |
| Type: | DAB.DCM2 |
| Model: | DCM2 50-1000 T 230/400/50 |
| Design: | twin-head, flanged, in-line |
| Flange nominal size: | DN 50 (PN 10 / PN 16) |
| Max. head (per designation): | ≈ 10 m |
| Motor poles: | 4 |
| Power supply: | 3 × 230/400 V, 50 Hz |
| Liquid temperature: | −15 … +140 °C |
| Max. glycol content: | 50 % |
| Max. operating pressure: | 16 bar |
| Protection rating / insulation class: | IP 55 / F |
Product rating
Be the first who will post an article to this item!
Discussion
Be the first who will post an article to this item!