Twin-head dry-rotor pump DAB DKLM 50-300 M, DN 50 flanges

Code: 105210444
Not rated Rating details
2 557,03 € –20 %
Zdvojené suchobežné čerpadlo DAB DKLM 50-300 M, príruby DN 50
2 557,03 € –20 % 2 045,62 € / pcs 1 663,11 € excl. VAT Measure price:
International delivery
To order (1-2 weeks)

Detailed information

Product detailed description

DAB DKLM 50-300 M (code 105210444) is a twin-head dry-rotor pump from DAB, DKLM series, in a flanged design with DN 50 flanges. It belongs to the pumps for heating, air-conditioning, solar and hot-water systems.

Designation and hydraulics

  • DN 50 – nominal size of the flanges, PN 6 / PN 10 flanges with measuring ports
  • 300 – maximum head in centimetres, i.e. about 3 m
  • M – single-phase motor 1 × 220–240 V, 50 Hz

For the whole KL/DKL series the manufacturer states a flow of 2 to 67 m³/h and a head of up to 13.7 m.

Motor

Enclosed four-pole asynchronous motor cooled by external ventilation, protection rating IP 55, insulation class F, built to CEI 2-3. The single-phase version has built-in thermal protection and a capacitor.

Materials and operation

Pump casing and lantern are cast iron, the impeller is technopolymer. The motor shaft is AISI 316 and the mechanical seal is silicon carbide (SiC/SiC). The pumped liquid should be clean, free of solid and abrasive matter, non-aggressive, non-viscous, non-crystallising and chemically neutral; its temperature may be −15 to +120 °C and the operating pressure up to 10 bar. The connection is a job for a qualified electrician.

Technical data

Code105210444
ManufacturerDAB
TypeDAB.DKLM
ModelDKLM 50-300 M
Designtwin-head, flanged
Flange nominal sizeDN 50 (PN 6 / PN 10)
Max. head (per designation)≈ 3 m
Motor poles4
Power supply1 × 220–240 V, 50 Hz
Liquid temperature−15 … +120 °C
Max. operating pressure10 bar
Protection rating / insulation classIP 55 / F
Impeller materialtechnopolymer

Frequently asked questions

What does the number 300 in the designation DKLM 50-300 M mean?
It is the maximum head in centimetres, so according to the designation the pump reaches about 3 m. The actual duty point depends on the flow in the system.

What supply does the pump DKLM 50-300 M require?
The designation M means a single-phase motor supplied with 1 × 220–240 V, 50 Hz; a four-pole motor turns more slowly than a two-pole one.

Which liquid is suitable for this pump?
Clean water free of solid and abrasive matter, non-aggressive, non-viscous and non-crystallising, at −15 to +120 °C and an operating pressure of up to 10 bar.

Does the pump motor need external overload protection?
The single-phase version M has built-in thermal protection and a capacitor. For the three-phase versions T the manufacturer requires external overload protection.

Additional parameters

Category: DAB.DKLM,DKLP,KLM,KLP - Dry-Rotor Pumps - Various Systems
Warranty: 2 years
Code: 105210444
Manufacturer: DAB
Type: DAB.DKLM
Model: DKLM 50-300 M
Design: twin-head, flanged
Flange nominal size: DN 50 (PN 6 / PN 10)
Max. head (per designation): ≈ 3 m
Motor poles: 4
Power supply: 1 × 220–240 V, 50 Hz
Liquid temperature: −15 … +120 °C
Max. operating pressure: 10 bar
Protection rating / insulation class: IP 55 / F
Impeller material: technopolymer

Product rating

Be the first who will post an article to this item!

Do not fill out this field

How would you rate this product? Choose 1 to 5 stars, where 1 is the worst and 5 is the best rating.

Discussion

Be the first who will post an article to this item!

Do not fill out this field
Vytvořil Shoptet | Design Shoptak.cz.