Flanged pressure reducing valve BRA.F15.100 DN 80, PN 10/16, face-to-face 310 mm
Code: F15100080Product detailed description
The BRA.F15.100 pressure reducing valve in DN 80 (code F15100080) is used to reduce and stabilise pressure in larger water and compressed air networks. It holds the set outlet pressure regardless of flow and inlet pressure fluctuations, protecting sensitive parts of the network – for example when a low-pressure network is supplied from a high-pressure one or at the outlet of storage tanks.
Construction
- body and cover of ductile iron with RAL 5002 epoxy powder coating
- piston and shutter of AISI 303 stainless steel, seat of AISI 304, spring of 55SiCr6 steel
- NBR gasket and O-rings, stainless steel bolts and nuts
- self-cleaning piston and large expansion chamber against noise and cavitation
- pressure ports for measuring inlet and outlet pressure
Technical data
- pressure class PN 10/16, max. 16 bar, flanges to EN 1092 / ISO 7005
- outlet pressure setting 1.5 to 6 bar (blue spring)
- medium temperature 0 °C to +70 °C
- face-to-face length 310 mm, weight 24 kg, Kv 72 m³/h
- approved for drinking water
Installation
The valve is preferably installed horizontally between two shut-off valves, with a strainer upstream and a safety valve downstream. The pressure reduction ratio should not exceed 5:1 and the outlet pressure is set at zero flow. The valve size is selected according to the maximum flow rate, not the pipe diameter.
Technical data
| Code | F15100080 |
| Brand | IVAR |
| Type | BRA.F15.100 PN10/16 |
| Nominal size | DN 80 |
| Face-to-face length | 310 mm |
| Pressure class | PN 10/16 (max. 16 bar) |
| Outlet pressure setting | 1.5–6 bar |
| Operating temperature | 0 °C to +70 °C |
| Body material | ductile iron, RAL 5002 epoxy coating |
| Seal | NBR |
| Kv | 72 m³/h |
| Weight | 24 kg |
Frequently asked questions
What outlet pressure can be set?
The valve regulates the outlet pressure between 1.5 and 6 bar. It is set with the adjusting screw at zero flow – turning clockwise increases the pressure.
What should be installed together with the valve?
A strainer upstream, shut-off valves on both sides for maintenance and a safety valve downstream. The pipework must be cleaned before installation.
Can the valve be installed vertically?
The horizontal position is recommended because it reduces wear on the internal parts. The instructions allow vertical installation only when it is unavoidable.
Additional parameters
| Category: | BRA.F15.100 PN10/16 - Flanged pressure reducing valve |
|---|---|
| Warranty: | 2 years |
| Weight: | 24 kg |
| Code: | F15100080 |
| Brand: | IVAR |
| Type: | BRA.F15.100 PN10/16 |
| Nominal size: | DN 80 |
| Face-to-face length: | 310 mm |
| Pressure class: | PN 10/16 (max. 16 bar) |
| Outlet pressure setting: | 1.5–6 bar |
| Operating temperature: | 0 °C to +70 °C |
| Body material: | ductile iron, RAL 5002 epoxy coating |
| Seal: | NBR |
| Kv: | 72 m³/h |
| Weight: | 24 kg |
Product rating
Be the first who will post an article to this item!
Discussion
Be the first who will post an article to this item!
IVAR designs, develops and manufactures highly energy-efficient heating and plumbing systems. We have over 10,000 catalogue items - mass-produced products and unique items - in addition to customised systems and combinations of complex products. And it’s all “Made in Italy”.
Vision
To make life easier for our clients, our clients' customers and our employees, thanks to our ability to be constantly innovative.
Mission
To design and manufacture advanced hydronic solutions that reduce installation complexity and energy consumption.
“Made in Italy” adds value
IVAR has been producing heating and plumbing system components since 1985: valves for heating bodies, direct heat metering modules, heat cost allocators, pipes and fittings, substations for heating systems, distribution manifolds, radiant panel systems, and components for solar and geothermal systems. And it’s all “Made in Italy”.
Over 200 people are employed at our manufacturing facilities in Prevalle (in northern Italy’s Brescia province). The site has been designed to streamline our many production and operational stages.
The Italian headquarters also acts as a hub for the wider IVAR Group, set up with the goal of distributing products beyond Italy’s borders. The group now has 11 branches, in Australia, Belgium, China, Germany, the United Kingdom, the Czech Republic, Romania, Slovakia, Spain, the United States and Tunisia.
Know How
Research, development and numerous laboratory tests guarantee that our clients’ requests can be translated into new high-efficiency products.
The stages required for production take place internally, beginning with hot forming, which is carried out at our subsidiary Valmon Stampati. Our continuous implementation of projects under the Industry 4.0 initiative also allows us to take full advantage of new releases in technology and IT to improve our manufacturing efficiency.
As a company, IVAR is constantly evolving. Every day, we invest in strengthening our products, in improving our production processes and in attaining new patents and certifications.