Two-way zone valve SELTRON BVQ DN 25 with AQD actuator 230 V and AUX output signal, Kvs 60 – IVAR.TER-SELT
Code: 10.01.11.1015Product detailed description
IVAR.TER-SELT DN 25 with output signal (code 10.01.11.1015) combines the two-way ball valve BVQ from manufacturer SELTRON with the sliding actuator AQD. This version of the actuator has, in addition to the two-point ON/OFF control, an auxiliary switch AUX, so it provides an output signal for further regulation components while closing the circuit.
Where it is used
- zonal heating and cooling control in open/closed mode
- shut-off element in heating, ventilation and air conditioning (HVAC) systems
- shut-off of hot water preparation circuits
- blocking element in industrial processes and agriculture
Valve BVQ DN 25
The body has internal threads Rp 1" on both sides, a construction length of 81 mm and a flow coefficient Kvs of 60 m³/h. The stem is protected against withdrawal and sealed with three O-rings. The working fluid can have a temperature of 10 to 90 °C.
Actuator AQD
- 230 V~, torque 5 Nm, rotation by 90° in 13 s
- wiring: terminals 1 (N), 2 (L), 3 (OPEN), terminals 4 and 5 – auxiliary switch AUX with a load capacity of 2(1) A / 230 V AC
- power consumption 5 W, less than 0.25 W in standby
- manual mode by pressing the button – the motor disconnects and the valve is adjusted using a rotating controller, the position is marked on the actuator
- the opening direction can be reversed by a jumper under the rotating controller
- mounting on the valve without tools, a lock prevents unintentional release
- protection class IP42, protection class II according to EN 60730-1, cable 1 m
The actuator has passed 100,000 cycle testing and does not get damaged in case of valve blockage. It operates at ambient temperatures from 0 to +55 °C and humidity up to 85 % without condensation; if flooding is possible, it is mounted above the expected water level. Installation and electrical connection must be carried out only by a qualified person.
Technical parameters
| Code | 10.01.11.1015 |
| Manufacturer | SELTRON |
| Type | IVAR.TER-SELT |
| Configuration | two-way ball valve BVQ + actuator AQD with auxiliary switch |
| Nominal diameter | DN 25 |
| Connection | internal thread Rp 1" |
| Kvs | 60 m³/h |
| Valve construction length | 81 mm |
| Supply voltage | 230 V~ |
| Control | two-point ON/OFF + AUX |
| AUX load capacity | 2(1) A, 230 V AC |
| Torque | 5 Nm |
| Switching time | 13 s / 90° |
| Fluid temperature | 10–90 °C |
| Protection class | IP42 |
Frequently asked questions
How does this valve differ from the version without an output signal?
The actuator AQD in this version has an additional auxiliary switch AUX on terminals 4 and 5 with a load capacity of 2(1) A at 230 V AC. The valve, torque and switching time of 13 s are the same.
Can the valve be adjusted manually?
Yes. By pressing the manual mode button, the motor disconnects and the valve can be set to any position using the rotating controller; pressing again returns it to automatic operation.
Can the valve opening direction be changed?
Yes. After removing the rotating controller, the jumper is pulled out, rotated to the opposite position and pushed back in, without further tools.
Additional parameters
| Category: | two-way valves with actuator |
|---|---|
| Warranty: | 2 years |
| Availability: | In stock or at supplier |
| Code: | 10.01.11.1015 |
| Manufacturer: | SELTRON |
| Type: | IVAR.TER-SELT |
| Design: | 2-way BVQ ball valve + AQD actuator with auxiliary switch |
| Nominal diameter: | DN 25 |
| Connection: | female thread Rp 1" |
| Kvs: | 60 m³/h |
| Valve length: | 81 mm |
| Supply voltage: | 230 V~ |
| Control: | 2-point ON/OFF + AUX |
| AUX rating: | 2(1) A, 230 V AC |
| Torque: | 5 Nm |
| Running time: | 13 s / 90° |
| Fluid temperature: | 10–90 °C |
| Protection rating: | IP42 |
Product rating
Be the first who will post an article to this item!
Discussion